トラッキングによるRCDケースの火焰バタンおよび燒損特性
トラッキングによるRCDケースの火焰バタンおよび燒損特性
カテゴリ: 部門大会
論文No: 37
グループ名: 【B】平成18年電気学会電力・エネルギー部門大会講演論文集
発行日: 2006/09/13
タイトル(英語): Flame Patterns and damaged properties of RCD Cases by Tracking
著者名: Chung-Seog Choi (韓國電氣安全公社),Hyang-Kon Kim (韓國電氣安全公社),Kil-Mok Shong (韓國電氣安全公社),Dong-Woo Kim (韓國電氣安全公社)
著者名(英語): Choi Chung-Seog(Korea Electrical Safety Corporation),Kim Hyang-Kon(Korea Electrical Safety Corporation),Shong Kil-Mok(Korea Electrical Safety Corporation),Kim Dong-Woo(Korea Electrical Safety Corporation)
キーワード: Tracking|RCD|Flame Patterns|Electrical Fire
要約(日本語): In this paper, the flame patterns of residual current protective devices(RCDs) by tracking were analyzed. Pictures of tracking process were taken by High Speed Imaging System(HSIS), and fire patterns were observed by timeframe. During the tracking process of RCD, it seemed to explode just once in appearance, but in the results of HSIS analysis, a small fire broke out and disappeared repeatedly 35 times and a flash of light repeated 15 times. Finally, an explosion with a flash of light occurred and lots of particles were scattered. Electric muffle furnace was used for heat treatment of RCD cases. The surface characteristics of specimens due to heat treatment and tracking deterioration were taken by SEM(Scanning Electron Microscope). Chemical and thermal properties of these deteriorated specimens were analyzed by Fourier Transform Infrared Spectrometer(FT-IR), Differential Thermal Analyzer(DTA). The carbonization characteristics showed different chemical properties due to energy sources, and the results could be applicable to judge the accident causes.
PDFファイルサイズ: 5,155 Kバイト