A Method for Direct Computation CCT for TSA Based on Critical Generator Conditions
A Method for Direct Computation CCT for TSA Based on Critical Generator Conditions
カテゴリ: 研究会(論文単位)
論文No: PSE10111
グループ名: 【B】電力・エネルギー部門 電力系統技術研究会
発行日: 2010/09/29
タイトル(英語): A Method for Direct Computation CCT for TSA Based on Critical Generator Conditions
著者名: Priyadi Ardyono(広島大学),餘利野 直人(広島大学),Abdul Mutalib Ridzuan (広島大学),杉原 弘章(中国電力株式会社)
著者名(英語): Priyadi Ardyono(Hiroshima University),Yorino Naoto(Hiroshima University),Abdul Mutalib Ridzuan (Hiroshima University),Sugihara Hiroaki(Chugoku Electric Power Co.)
キーワード: Electric power system|Transient stability analysis|Critical clearing time|Critical trajectory method
要約(日本語): This paper proposes new techniques for critical trajectory method, a recent new method for obtaining critical clearing time (CCT) for transient stability analysis (TSA). A specific feature of the proposed method lies in its ability to provide exact CCT without approximations since no such methods have existed so far. The method is based on the computation of the critical trajectory, which is defined as the trajectory that starts from a point on a fault-on trajectory at CCT and reaches an end point. There are few possible methods for the treatment of the end point conditions, of the methods are investigated in terms of accuracy of CCT and computational efficiency. It is shown that the proposed methods successfully provide the exact CCT for Xd’ generator model with and without controllers which agrees with the conventional numerical simulation method.
原稿種別: 日本語
PDFファイルサイズ: 1,118 Kバイト