CF3Iガスの放電による副生成物の発生と絶縁特性への影響
CF3Iガスの放電による副生成物の発生と絶縁特性への影響
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2011/10/01
タイトル(英語): By-product Generation through Electrical Discharge in CF3I Gas and its Effect to Insulation Characteristics
著者名: 武田 敏信(東京大学大学院 工学系研究科 電気系工学専攻),松岡 成居(東京大学大学院 工学系研究科 電気系工学専攻),熊田 亜紀子(東京大学大学院 工学系研究科 電気系工学専攻),日高 邦彦(東京大学大学院 工学系研究科 電気系工学専攻)
著者名(英語): Toshinobu Takeda (Department of Electrical Engineering and Information Systems, The University of Tokyo), Shigeyasu Matsuoka (Department of Electrical Engineering and Information Systems, The University of Tokyo), Akiko Kumada (Department of Electrical Engineering and Information Systems, The University of Tokyo), Kunihiko Hidaka (Department of Electrical Engineering and Information Systems, The University of Tokyo)
キーワード: 代替SF6,CF3I,ガス分析,副生成物,沿面放電 substitution of SF6,CF3I,GC/MS,by-product,surface discharge
要約(英語): CF3I gas, which is one of promising SF6 substitutions, is investigated from the view point of by-product generated in gas discharge, since its global warming potential (GWP) is quite low and its insulation performance is equivalent or superior to SF6 gas. The insulation performance of CF3I gas is examined through measuring sparkover voltage in various electric fields and flashover voltage on the surface of insulating material together with analyzing by-products of CF3I gas. Gas chromatography analysis shows that C2F6, C2F4, CHF3, C3F8, C3F6, and C2F5I are generated by the sparkover and the flashover. The sparkover voltage after 1300 times sparkover in uniform electric field is decreased by 11%. The flashover voltage for a virgin insulator in CF3I gas is almost equal to that in SF6 gas. The flashover voltage in CF3I gas is, however, 0.6 times lower than that in SF6 gas, when the number of surface flashover is increased.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.131 No.10 (2011)
本誌掲載ページ: 859-864 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/131/10/131_10_859/_article/-char/ja/
受取状況を読み込めませんでした