インパルス発生装置を用いた配電用避雷器の故障判定方法
インパルス発生装置を用いた配電用避雷器の故障判定方法
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2014/05/01
タイトル(英語): A Detection Method of Damaged Distribution Surge Arresters Using an Impulse Generator
著者名: 松浦 進(北陸電力(株)技術開発研究所),島崎 克彦(北陸電力(株)高岡支社),杉本 仁志(北陸電力(株)技術開発研究所)
著者名(英語): Susumu Matsuura (Engineering Resarch & Development Center, Hokuriku Electric Power Company), Katsuhiko Shimasaki (Takaoka Branch, Hokuriku Electric Power Company), Hitoshi Sugimoto (Engineering Resarch & Development Center, Hokuriku Electric Power Company)
キーワード: 配電線,雷,避雷器,故障,判定方法,インパルス発生装置 distribution line,lightning,surge arrester,damage,detection method,impulse generator
要約(英語): Distribution surge arresters with an internal series gap have been installed on Japanese distribution lines in high density for reducing lightning-related overvoltages. In contrast, surge arresters are sometimes damaged by direct lightning strokes, particularly in winter. Measurement of insulation resistance between terminals of the surge arrester and measurement of DC discharge voltage of the surge arrester are generally adopted to detect damaged arresters. However, if metal-oxide (MO) varistors are damaged and the internal series gap is not damaged, it is difficult to detect damaged arresters by two conventional methods.Therefore, this paper presents the proposed detection method which can accurately detect damaged arresters. In the proposed method, first, the voltage between terminals of the surge arrester is measured when the output of an impulse generator is applied to the surge arrester. Secondly, the damaged arrester is detected by the comparison between its voltage waveform and the voltage waveform of the non-damaged arrester. The detection rate of damaged arresters by the proposed method is remarkably higher than those by two conventional methods.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.134 No.5 (2014)
本誌掲載ページ: 412-418 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/134/5/134_412/_article/-char/ja/
受取状況を読み込めませんでした