交流重畳法の22/33kV級CVケーブルの劣化診断への応用に関する検討
交流重畳法の22/33kV級CVケーブルの劣化診断への応用に関する検討
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2014/05/01
タイトル(英語): A Study on Application of AC Superposition Method to Degradation Diagnosis of 22/33kV Class XLPE Cables
著者名: 熊澤 孝夫(中部電力(株)エネルギー応用研究所)
著者名(英語): Takao Kumazawa (Energy Applications R&D Center, Chubu Electric Power Co., Inc.)
キーワード: CVケーブル,水トリー,劣化診断,交流重畳法 XLPE cable,water tree,degradation diagnosis,AC superposition method
要約(英語): Water trees in insulator of XLPE cable may considerably reduce the dielectric breakdown voltage, thus being an important lifetime-governing factor. AC superposition method we have investigated is a new technique for hot-line diagnosis of 6.6kV XLPE cables, and the diagnostic apparatus using this technique is now widely used in the field of distribution line. In order to study an application of the AC superposition method to degradation diagnosis of 22/33kV class XLPE cables, we measured deterioration signals of the cables with water trees by modified above diagnostic apparatus. The deterioration signals, hereafter called “AC superposition current”, were generated by an amplitude modulation effect due to non-linear resistance of water tree. Moreover, we evaluated the relationship between the AC superposition current and the AC breakdown voltage. It is difficult to judge whether the correlation of them is present or not because of uneven distribution of the measured data. However, the AC superposition current tends to increase linearly with a decrease in the residual thickness of the insulator. For example, the AC superposition current was about 40nA when the residual thickness decreased to 3mm. Thus, we consider that the AC superposition method is available for degradation diagnosis of 22/33kV class XLPE cables.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.134 No.5 (2014)
本誌掲載ページ: 443-449 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/134/5/134_443/_article/-char/ja/
受取状況を読み込めませんでした