続流遮断型アークホーンの遮断時間短縮と強度向上
続流遮断型アークホーンの遮断時間短縮と強度向上
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2019/07/01
タイトル(英語): Interruption Time Reduction and Strength Improvement of Fault Current Interrupting Arcing Horns
著者名: 粟津 隼人(関西電力(株)),上原 実(日本カタン(株)),大髙 聡也((一財)電力中央研究所)
著者名(英語): Hayato Awazu (Kansai Electric Power Co., Inc.), Minoru Uehara (Nippon Katan Co., Ltd.), Toshiya Ohtaka (Central Research Institute of Electric Power Industry)
キーワード: 続流遮断型アークホーン,架空送電線,耐雷 fault current interrupting arcing horns,overhead transmission line,lightning protection
要約(英語): Fault Current Interrupting Arcing Horns (FCIAH) for 77kV overhead transmission lines are a countermeasure against lightning damage which break fault current within an AC cycle, and greatly contribute to reducing power interruption and instantaneous voltage drop. This paper has presented that reducing the number of interruption core from 2 to 1 reduced the cost of FCIAH, and changing the structure of interruption core resulted in reducing the interruption time from 1.0 cycle to 0.5 cycle and improving the current value from 10kA to 31.5kA when the interruption core was damaged.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.139 No.7 (2019)
本誌掲載ページ: 457-460 p
原稿種別: 解説/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/139/7/139_457/_article/-char/ja/