EDCによる出力応動を考慮したLFC発電機の効果的な制御方法
EDCによる出力応動を考慮したLFC発電機の効果的な制御方法
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2020/07/01
タイトル(英語): A Method for Effective Control of LFC Generator in Consideration of Power Output Response to EDC
著者名: 斉田 賢(名古屋大学大学院工学研究科電気工学専攻),今中 政輝(名古屋大学 未来材料・システム研究所),栗本 宗明(名古屋大学 未来材料・システム研究所),杉本 重幸(名古屋大学 未来材料・システム研究所),加藤 丈佳(名古屋大学 未来材料・システム研究所),秦 幸一郎(中部電力(株)技術開発本部 電力技術研究所),中地 芳紀(中部電力(株)技術開発本部 電力技術研究所),Suresh Chand Verma(中部電力(株)技術開発本部 電力技術研究所)
著者名(英語): Masaru Saida (Dept. of Electrical Eng., Grad School of Eng., Nagoya University), Masaki Imanaka (Institute of Materials and Systems for Sustainability, Nagoya Univercity), Muneaki Kurimoto (Institute of Materials and Systems for Sustainability, Nagoya Univercity), Shigeyuki Sugimoto (Institute of Materials and Systems for Sustainability, Nagoya Univercity), Takeyoshi Kato (Institute of Materials and Systems for Sustainability, Nagoya Univercity), Kouichiro Hata (Chubu Electric Power Co., Inc.), Yoshiki Nakachi (Chubu Electric Power Co., Inc.), Suresh Chand Verma (Chubu Electric Power Co., Inc.)
キーワード: 負荷周波数制御,経済負荷配分制御,ランプレート,太陽光発電 load-frequency control,economic-load dispatching control,ramp-rate,photovoltaic power generation
要約(英語): Due to the increasing capacity of uncontrollable renewable generators such as photovoltaic power generations, the portion of controllable generators decreases significantly especially in daytime, resulting in the threat of frequency fluctuation exceeding the acceptable range. Implementation of sophisticated power output control method of controllable generators is one of the most practically feasible solutions. This paper proposes a method to load-frequency control (LFC) in consideration of prospected power output response to economic-load dispatching control (EDC). When the prepared LFC capacity is not so sufficient in terms of ramp-rate, the difference between commanded LFC signal and actual power output is accumulated, resulting in unexpected and undesirable power output change later on. The numerical simulation using AGC30 model demonstrates that the proposed method works well by eliminating such an unusable LFC command in consideration of prospected power output response to EDC.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.140 No.7 (2020)
本誌掲載ページ: 572-582 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/140/7/140_572/_article/-char/ja/