柱上変圧器の容量超過回避を目的とした需要家蓄電池の分散型充放電制御手法
柱上変圧器の容量超過回避を目的とした需要家蓄電池の分散型充放電制御手法
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2020/08/01
タイトル(英語): Decentralized BESS Charging and Discharging Control Method for Avoiding Pole Transformer Overcapacity
著者名: 大久保 里矩(早稲田大学),芳澤 信哉(早稲田大学),林 泰弘(早稲田大学),河野 俊介(三菱電機(株)先端技術総合研究所),松田 啓史(三菱電機(株)電力・産業システム事業本部),板屋 伸彦(三菱電機(株)電力・産業システム事業本部),高野 富裕(三菱電機(株)先端技術総合研究所)
著者名(英語): Riku Okubo (Waseda Univeristy), Shinya Yoshizawa (Waseda Univeristy), Yasuhiro Hayashi (Waseda Univeristy), Shunsuke Kawano (Advanced Technology R&D Center, Mitsubishi Electric Corp.), Keishi Matsuda (Energy & Industrial System Group, Mitsubishi Electric Corp.), Nobuhiko Itaya (Energy & Industrial System Group, Mitsubishi Electric Corp.), Tomihiro Takano (Advanced Technology R&D Center, Mitsubishi Electric Corp.)
キーワード: 蓄電池充放電方法,柱上変圧器容量超過,分散型制御,逆潮流制御 BESS charging and discharging method,pole transformer overcapacity,decentralized control,reverse power flow control
要約(英語): This paper proposes a decentralized charging and discharging control method of a battery energy storage system (BESS) to prevent the over-capacity of a pole transformer (Pole-Tr) in low-voltage (LV) distribution systems due to reverse power flow from the photovoltaic generation (PV) system. A distribution system operator (DSO) provides the charging/discharging parameters determined by using only the LV-distribution system configuration and the PV/BESS capacity to the customers and each BESS automatically controls the charging/discharging power according to the provided parameters. The charging parameter is defined in the relationship between the state-of-charge (SoC) and the charging threshold ε as the SoC-ε curve, and a total of three SoC-ε curves for the different objectives are prepared. In the charging phase, the BESS selects one SoC-ε curve every minute and determines the charging power based on the charging threshold ε and the present SoC. In the discharging phase, the BESS operates in the load-following discharging and SoC control discharging to adjust the SoC for the prevention of the over-capacity of Pole-Tr. The proposed method is tested on several types of LV-distribution systems, and the numerical simulation results demonstrate that the proposed method can prevent the over-capacity of Pole-Tr and maintain the high charging amount of BESSs.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.140 No.8 (2020)
本誌掲載ページ: 638-649 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/140/8/140_638/_article/-char/ja/
受取状況を読み込めませんでした