高エネルギー雷撃を模擬した直流アークによる高張力・高耐食OPGWの素線溶断特性
高エネルギー雷撃を模擬した直流アークによる高張力・高耐食OPGWの素線溶断特性
カテゴリ: 論文誌(論文単位)
グループ名: 【B】電力・エネルギー部門
発行日: 2021/06/01
タイトル(英語): Melting and Breaking Characteristics of Strands of High-strength and High-corrosion-resistant OPGW due to DC Arc Discharge Simulating High-energy Lightning Strike
著者名: 岩田 幹正((一財)電力中央研究所),大高 聡也((一財)電力中央研究所),合田 豊((一財)電力中央研究所),山上 進(電源開発送変電ネットワーク(株)),加藤 厚志(電源開発送変電ネットワーク(株)),長野 宏治(住友電気工業(株))
著者名(英語): Mikimasa Iwata (Central Research Institute of Electric Power Industry (CRIEPI)), Toshiya Ohtaka (Central Research Institute of Electric Power Industry (CRIEPI)), Yutaka Goda (Central Research Institute of Electric Power Industry (CRIEPI)), Susumu Yamagami
キーワード: 雷撃,直流アーク,高張力・高耐食OPGW,素線溶断 lightning strike,DC arc,high-strength and high-corrosion-resistant OPGW,melting and breaking of strands
要約(英語): Metal strands of composite fiber-optic ground wire (OPGW) are sometimes melted and broken by high-energy lightning strikes. Direct current (DC) arc tests simulating the lightning strikes have thus been performed to obtain the melting and breaking characteristics of OPGW strands. J-Power Transmission Network Co., Ltd. has developed high-strength and high-corrosion-resistant OPGW for long-span 500kV overhead transmission lines crossing straits. This paper describes the melting and breaking characteristics of the OPGW strands due to DC arc discharge simulating high-energy lightning strike. In this research, the tests were performed using two kinds of arc, one was the arc supposing summer lightning whose polarity was negative with a relatively short duration, and the other was the arc supposing winter lightning whose polarity was positive with a relatively long duration. Furthermore, the calculations regarding the melting and breaking of OPGW strands were carried out, and the calculation results showed a tendency similar to the test results.
本誌: 電気学会論文誌B(電力・エネルギー部門誌) Vol.141 No.6 (2021)
本誌掲載ページ: 492-499 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejpes/141/6/141_492/_article/-char/ja/