インバータ出力配線へのシールドケーブルの適用に関する検討
インバータ出力配線へのシールドケーブルの適用に関する検討
カテゴリ: 論文誌(論文単位)
グループ名: 【D】産業応用部門
発行日: 2012/07/01
タイトル(英語): A Study on the Use of Shielded Cables in Inverter Output Wiring
著者名: 土田 崇((株)関電工/長岡技術科学大学)
著者名(英語): Takashi Tsuchida (KANDENKO Co., Ltd./Nagaoka University of Technology)
キーワード: コモンモード電流,シールドケーブル,接地系統,PWMインバータ common-mode current,shielded cable,grounding system,PWM inverter
要約(英語): An increasing number of voltage-driven-type PWM inverters have begun to be used recently for electrical equipment in buildings owing to energy conservation considerations. However, common-mode currents originate from this type of inverters, and problems due to such common-mode currents flowing in grounding systems of buildings have increased with their increased use. While it is necessary to study countermeasures to overcome these problems by considering the entire circuit in question (since common-mode currents flow in the whole circuit including power-supply and grounding systems), there seem to have been very few such studies. In this study, the author constructed a test circuit comprising a PWM inverter, an induction motor, and grounding electrodes, and he studied measures to suppress common-mode currents by using shielded cables and a grounding system. He also studied a method for grounding the shielding of the shielded cables used for the power supply from the inverter to the motor suppressing common-mode currents.
本誌: 電気学会論文誌D(産業応用部門誌) Vol.132 No.7 (2012)
本誌掲載ページ: 718-726 p
原稿種別: 論文/日本語
電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejias/132/7/132_718/_article/-char/ja/