商品情報にスキップ
1 1

Control Strategy for Modular Multilevel Converter based on Single-phase Power Factor Correction Converter

Control Strategy for Modular Multilevel Converter based on Single-phase Power Factor Correction Converter

通常価格 ¥770 JPY
通常価格 セール価格 ¥770 JPY
セール 売り切れ
税込

カテゴリ: 論文誌(論文単位)

グループ名: 【D】産業応用部門(英文)

発行日: 2017/01/01

タイトル(英語): Control Strategy for Modular Multilevel Converter based on Single-phase Power Factor Correction Converter

著者名: Toshiki Nakanishi (Nagaoka University of Technology), Jun-ichi Itoh (Nagaoka University of Technology)

著者名(英語): Toshiki Nakanishi (Nagaoka University of Technology), Jun-ichi Itoh (Nagaoka University of Technology)

キーワード: modular multilevel converter,power factor correction converter,step-down rectifier,DC micro-grid,DC distribution systems

要約(英語): This paper proposes a novel control strategy for a step-down rectifier that applies a modular multilevel converter (MMC). This paper first discusses the circuit configuration and the proposed control method. The main part of the control system is based on the control method for the single-phase power factor correction converter (PFC converter), which means that the conventional control techniques of the single-phase PFC converter can be simply applied to the MMC. The control elements which achieve step-down rectification and capacitor voltage balancing are added to the main part. Besides, in capacitor voltage balancing of the proposed control method, it is not necessary to design the control parameters. In addition, the operation of the proposed step-down rectifier is confirmed by the simulation. The simulation results show that the proposed converter achieves step-down rectification from the grid voltage of 6.6kV to the DC voltage of 400V. Moreover, the step-down rectifier maintains all capacitor voltages constant. Finally, a fundamental operation is confirmed by experiments using a miniature model. As the results, the step-down rectifier converts from the input grid voltage of 200V to the output DC voltage of 75V. Besides, the proposed step-down rectifier maintains the capacitor voltage of each cell to the voltage command of 130V. The maximum error between the voltage command of the cell capacitor and the measured voltage is less than 2%.

本誌: IEEJ Journal of Industry Applications Vol.6 No.1 (2017) Special Issue on “Motor Drive and its Related Technologies”

本誌掲載ページ: 46-57 p

原稿種別: 論文/英語

電子版へのリンク: https://www.jstage.jst.go.jp/article/ieejjia/6/1/6_46/_article/-char/ja/

販売タイプ
書籍サイズ
ページ数
詳細を表示する