A Study on Interrupting Conditions Imposed on a Circuit Breaker with Fault Current Limiter
A Study on Interrupting Conditions Imposed on a Circuit Breaker with Fault Current Limiter
カテゴリ: 全国大会
論文No: 6-280
グループ名: 【全国大会】平成13年電気学会全国大会論文集
発行日: 2001/03/21
タイトル(英語): A Study on Interrupting Conditions Imposed on a Circuit Breaker with Fault Current Limiter
著者名: Evenson Calixte(Nagoya University),Yasunobu Yokomizu(Nagoya University),Hirotaka Shimizu(Nagoya University),Toshiro Matsumura(Nagoya University),Hideki Fujita(Chubu Electric Power Company Co.,Inc.)
著者名(英語): Evenson Calixte(Nagoya University),Yasunobu Yokomizu(Nagoya University),Hirotaka Shimizu(Nagoya University),Toshiro Matsumura(Nagoya University),Hideki Fujita(Chubu Electric Power Company Co.,Inc.)
要約(日本語): This report investigates the influence of the location of a fault current limiter (FCL) on the interrupting condition imposed on a circuit breaker. The interrupting condition was found to be almost independent of the location of the FCL. The resistive FCL is considered to offer advantage in relaxing the interrupting condition of the circuit breaker. However, the inductive FCL would not necessarily be effective in relaxing the interrupting condition of the circuit breaker.