Breaking Duty Imposed on Circuit Breaker with Resistive Fault Current Limiter under Generator-Fed Fault Condition

Breaking Duty Imposed on Circuit Breaker with Resistive Fault Current Limiter under Generator-Fed Fault Condition

通常価格 ¥440 JPY
通常価格 セール価格 ¥440 JPY
セール 売り切れ
税込

カテゴリ: 全国大会

論文No: 6-253

グループ名: 【全国大会】平成15年電気学会全国大会論文集

発行日: 2003/03/17

タイトル(英語): Breaking Duty Imposed on Circuit Breaker with Resistive Fault Current Limiter under Generator-Fed Fault Condition

著者名: Evenson Calixte(Nagoya University),Shuichi Hirata(Nagoya University),Yasunobu Yokomizu(Nagoya University),Toshiro Matsumura(Nagoya University),Hideki Fujita(Chubu Electric Power Co.,Inc.)

著者名(英語): Evenson Calixte(Nagoya University),Shuichi Hirata(Nagoya University),Yasunobu Yokomizu(Nagoya University),Toshiro Matsumura(Nagoya University),Hideki Fujita(Chubu Electric Power Co.,Inc.)

要約(日本語): The present paper looks at the interrupting duty imposed on a circuit breaker connected with a resistive FCL when a fault occurs between the FCL and a step-up transformer. The results of this study showed that the resistive FCL can be used to avoid the occurrence of delayed current zero. Also, the presence of the FCL makes it possible to use a generator circuit breaker having a lower interrupting capability compared to that in the absence of the FCL.