Partial discharge properties in low vacuum region of vacuum interrupter
Partial discharge properties in low vacuum region of vacuum interrupter
カテゴリ: 全国大会
論文No: 6-201
グループ名: 【全国大会】平成16年電気学会全国大会論文集
発行日: 2004/03/17
タイトル(英語): Partial discharge properties in low vacuum region of vacuum interrupter
著者名: Mohamad Kamarol Mohd Jamil (九州工業大学),大塚信也 (九州工業大学),趙孟佑 (九州工業大学),匹田 政幸(九州工業大学),榊 正幸(日本AEパワーシステムズ),斉藤 仁(日本AEパワーシステムズ)
著者名(英語): Mohamad Kamarol Mohd Jamil (Kyushu Institute of Technology),Shinya Ohtsuka(Kyushu Institute of Technology),Mengu Cho(Kyushu Institute of Technology),Masayuki Hikita(Kyushu Institute of Technology),Masayuki Sakaki(Japan AE Power Systems Corporation),Hitoshi Saitoh(Japan AE Power Systems Corporation)
キーワード: 真空遮断機|低真空|部分放電
要約(日本語): Basically vacuum interrupter (VI) is designed to keep its internal pressure at the order of 10-7~10-8 Torr. If leak is occurring, the air or the gas surrounding the VI may invade and would increase the internal pressure. The level of vacuum will deteriorate and the insulation performance will decrease. Due to these phenomena the partial discharge (PD) which will lead to the breakdown might occur. The study on the reliability of vacuum interrupter such a detection of a slow leak has been carried out [1] but the study of PD properties on a leak of VI is still insufficient. In this report, clarification of PD occurring at low vacuum is carried out. Three levels of air pressure with three strips of VI were used to simulate the leakage of the VI at 1, 5 and 20 Torr.
原稿種別: 日本語
PDFファイルサイズ: 949 Kバイト
受取状況を読み込めませんでした