EMTP Transformer Equivalent Circuit for TRV Calculation with 50MVA Short Circuit Test Transformer
EMTP Transformer Equivalent Circuit for TRV Calculation with 50MVA Short Circuit Test Transformer
カテゴリ: 全国大会
論文No: 6-257
グループ名: 【全国大会】平成23年電気学会全国大会論文集
発行日: 2011/03/05
タイトル(英語): EMTP Transformer Equivalent Circuit for TRV Calculation with 50MVA Short Circuit Test Transformer
著者名: Thein Myo Min (九州工業大学),戸田弘明 (九州工業大学),匹田政幸 (九州工業大学),池田久利 (東京大学),萩森英一 (東芝),腰塚 正 (東芝)
キーワード: transformer limited fault|frequency response analysis|transformer equivalent circuit|transient recovery voltage
要約(日本語): To study transient recovery voltage (TRV) at transformer limited fault (TLF) interrupting condition, EMTP transformer equivalent circuit was constructed using the impedance values which were calculated from frequency response analysis (FRA). The purpose of the study is to understand clearly the TRV of TLF condition. The study results with 4kVA and 300kVA transformers showed the amplitude factors (A.F) are about 1.4. In this paper the simulation result of TRV with 50 MVA transformer will be presented.
原稿種別: 日本語
PDFファイルサイズ: 1,288 Kバイト
受取状況を読み込めませんでした