Research on Insulation Defect Detection Effectiveness of On-site Impulse Voltage Test for GIS Equipment
Research on Insulation Defect Detection Effectiveness of On-site Impulse Voltage Test for GIS Equipment
カテゴリ: 全国大会
論文No: 7-078
グループ名: 【全国大会】平成29年電気学会全国大会論文集
発行日: 2017/03/05
タイトル(英語): Research on Insulation Defect Detection Effectiveness of On-site Impulse Voltage Test for GIS Equipment
著者名: Tao Wen(Tokushima University),Naoyuki Shimomura(Tokushima University),Kenji Teranishi(Tokushima University),Qiaogen Zhang(Xi’an Jiaotong University)
著者名(英語): Tao Wen(Tokushima University),Naoyuki Shimomura(Tokushima University),Kenji Teranishi(Tokushima University),Qiaogen Zhang(Xi'an Jiaotong University)
キーワード: ガス絶縁金属閉鎖式開閉装置|インパルス耐電圧試験|絶縁欠陥
要約(日本語): The breakdown characteristics of SF6 in a highly inhomogeneous electric field under double-exponential impulses with different wavefront times were investigated to evaluate the effectiveness of the non-standard LI test in detecting defects in GIS. Results show that as Tf increases, the 50% breakdown voltages decrease to a minimum value and then increase. When Tf exceeds 2.0 μs, the 50% breakdown voltage is higher than that of standard LI obviously. The standard or impulse LI test with Tf ? 1.56 μs is to be preferred for installation detection, for it offers a greater probability of detecting insulation defects.
原稿種別: 英語
PDFファイルサイズ: 421 Kバイト
受取状況を読み込めませんでした